The restraint values of frequency spectrum(vacant state)

  The scales of temperature and humidity in clean room

Room property
Temperature(℃)
humidity(%)
Winter
Summer
Winter
Summer

Temperature and humidity required clean room

Determined by the production technique

No temperature and humidity required clean room

20-22
24-26
30-50
50-70
The room for people purification and living
16-20
26-30

 

 

 
 
Air flow pattern and air volume(static state)

Air cleanliness class

Air flow pattern

Average air speed(m/s)

Air change rate(h-1)

1-4

Non-unidirectional flow

0.3-0.5

-

5

Non-unidirectional flow

0.2-0.5

-

6

Unidirectional flow

-

50-60

7

Unidirectional flow

-

15-25

8-9

Unidirectional flow

-

10-15

Note:①Air change rate is fit for the clean room whose height is less than 4.0m.

  ②If there are few people in the room, or heat sources are not enough, lower limit value will be used.